Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/06/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevention Inspection. Camille Lujan 888-7597

Outstanding Inspections

Case Number: T09FR01548
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
05/06/2009 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required IFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____1. Lower the storage located in the back room above the restroom. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
05/06/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____1. Remove the breaker stops located in the electrical panels.
05/06/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Service and tag all portable fire extinguishers.
05/06/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The north EXIT sign located by the sandals shall be internally illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01548
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/27/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.