Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/05/2009

Applicant:

SANTA CRUZ PLAZA LLC

Description:

Desert Fitness fire inspection.

Outstanding Inspections

Case Number: T09FR01539
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
VIOL - MEANS OF EGRESS None Not Inspected
05/05/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
05/05/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact.
05/05/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes ___ Provide covers for all unused electrical breaker outlets.
05/05/2009 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles.
05/05/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request
05/05/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ___ Remove locking hardware from door by group fitnes s group room.
05/05/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.
05/05/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01539
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/05/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
05/26/2009 INSP - REINSPECTION JLOYA Approved All violations abated.