Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/04/2009

Applicant:

PARK MALL LLC

Description:

Full Inspection conducted 5/1/09 Wetzels Pretzels, #426 I have received a copy of this report and understand the corrections needed: ________________ Business Owner: Steve Leibson, Phone: 748-1735 Inspector: __________________, Captain: _____________ David Greenleaf, MA 23 If you have any questions please call 791-4502. Approved: ________ Re-inspection: __/__/__ (or after)

Outstanding Inspections

Case Number: T09FR01536
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
05/01/2009 INSP - FULL DGREENLE Violation TFC 904.11.6.3 - Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ Clean hood system and keep records of periodical cleanings. TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. NOTE: The Tucson Fire Code does not require this type of occupancy to have portable fire extinguishers. HOWEVER... if, due to lease or insurance requirements, you choose to keep it, it is recommended that you re-locate it so that it is along the route of escape between the oven and the exit. _____ Adjust escutchen around sprinkler head above mop sink. _____ Clean dust from and adjust escutchen around sprinkler head above oven. TFC 605.3 - Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. TFC 315.2.1 - Ceiling clearance. Storage shall be maintained ... a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ Clear area around sprinkler head in storeroom. TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. _____ Repair or replace emergency light in back room.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01536
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/21/2009 INSP - REINSPECTION DGREENLE Approved