Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/04/2009

Applicant:

US REIF TUCSON COMMERCE CENTER AZ LLC

Description:

New Warehouse Occupancy

Outstanding Inspections

Case Number: T09FR01528
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
05/04/2009 VIOL - FIRE SERVICE FEATURES GDAURIA Violation 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. -- Instal an approved FD lock box at north door
05/04/2009 VIOL - FIRE SERVICE FEATURES GDAURIA Violation TFC505.1 Address numbers. -- install address #'s at all auxillary doors of bldg (4")
05/04/2009 VIOL - FIRE SERVICE FEATURES GDAURIA Violation TFC505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification -- Add Suite lettering (A / B) to the building's south side
05/04/2009 VIOL - MEANS OF EGRESS GDAURIA Violation 1006.1 Illumination required. The means of egress, the exit discharge, shall be illuminated at all times the space served by the means of egress is occupied. -- verify that emergency egress lighting kits function properly
05/04/2009 VIOL - MEANS OF EGRESS GDAURIA Violation 1011.1 Where required. -- EXIT SIGNS -- Remove invalid exit sign @ NW corner
05/04/2009 VIOL - MEANS OF EGRESS GDAURIA Violation TFC1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. -- Raise all exit signs to approx 16' for visibility
05/04/2009 VIOL - HAZARDOUS MATERIALS,GEN GDAURIA Violation TFC 2703.5 Hazard identification signs. -- Install NFPA 704 placards on East and Northy entrances

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01528
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/22/2009 INSP - FULL GDAURIA Approved