Case: T09FR01528
Case Details
Entered Date:
05/04/2009
Applicant:
US REIF TUCSON COMMERCE CENTER AZ LLC
Description:
New Warehouse Occupancy
Outstanding Inspections
Case Number: T09FR01528
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/04/2009 | VIOL - FIRE SERVICE FEATURES | GDAURIA | Violation | 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. -- Instal an approved FD lock box at north door |
05/04/2009 | VIOL - FIRE SERVICE FEATURES | GDAURIA | Violation | TFC505.1 Address numbers. -- install address #'s at all auxillary doors of bldg (4") |
05/04/2009 | VIOL - FIRE SERVICE FEATURES | GDAURIA | Violation | TFC505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification -- Add Suite lettering (A / B) to the building's south side |
05/04/2009 | VIOL - MEANS OF EGRESS | GDAURIA | Violation | 1006.1 Illumination required. The means of egress, the exit discharge, shall be illuminated at all times the space served by the means of egress is occupied. -- verify that emergency egress lighting kits function properly |
05/04/2009 | VIOL - MEANS OF EGRESS | GDAURIA | Violation | 1011.1 Where required. -- EXIT SIGNS -- Remove invalid exit sign @ NW corner |
05/04/2009 | VIOL - MEANS OF EGRESS | GDAURIA | Violation | TFC1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. -- Raise all exit signs to approx 16' for visibility |
05/04/2009 | VIOL - HAZARDOUS MATERIALS,GEN | GDAURIA | Violation | TFC 2703.5 Hazard identification signs. -- Install NFPA 704 placards on East and Northy entrances |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01528
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2009 | INSP - FULL | GDAURIA | Approved |