Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/30/2009

Applicant:

FLV PROPERTY MANAGEMENT LLC

Description:

MND auto repair fire inspection.

Outstanding Inspections

Case Number: T09FR01501
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
04/30/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
04/30/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation Blocked electrical panel: 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01501
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
04/30/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
05/14/2009 INSP - REINSPECTION JLOYA Approved All violations abated.