Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/23/2009

Applicant:

MC HENRY DAVID J & MARY JANE JT/RS

Description:

Rubs Bill Burden 520-885-2224 Inspector M. Pursley

Outstanding Inspections

Case Number: T09FR01418
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
04/23/2009 INSP - FULL MPURSLEY Correction Required Initial inspection 4/22/09 Reinspection due 5/5/09
04/23/2009 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters. 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical outlets.
04/23/2009 VIOL - FIRE RESIST.RATED CONST MPURSLEY Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile
04/23/2009 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the double-key lock and replace with an approved locking device such as, thumb turn lock or panic hardware Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01418
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/29/2009 INSP - REINSPECTION MPURSLEY Approved