Case: T09FR01406
Case Details
Entered Date:
04/23/2009
Applicant:
DHS PROPERTY INVESTMENTS LTD PARTNERSHIP
Description:
self insp
Outstanding Inspections
Case Number: T09FR01406
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | IFC 1008.1.8.3 #2.2: A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background |
04/23/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | IFC 1027.5: Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such |
04/23/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | IFC 605.3: Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated |
04/23/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | IFC 605.5: Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances |
04/23/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | IFC 901.6: If you have a fire extinguisher in your building, has it been serviced within the past 12 months? Fire extinguishers shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. |