Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/22/2009

Applicant:

BROWN GAROLD C FAMILY LTD

Description:

West Med full fire inspection.

Outstanding Inspections

Case Number: T09FR01387
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
04/22/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
04/22/2009 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 309.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger.
04/22/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
04/22/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
04/22/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
04/22/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ___Return Class II standpipe hose into service by qualified presonnel.
04/22/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities
04/22/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.
04/22/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
04/22/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
04/22/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1023.6 Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way. __Tool room exit
04/22/2009 VIOL - WELDING & OTHER HOT WRK JLOYA Violation 2603.1 General. Hot work conditions and operations shall comply with this chapter. ___Copy of IFC chapter 26 provided for reference regarding requirements for hot work.
04/22/2009 VIOL - FLAMMABLE LIQUIDS JLOYA Violation 3404.3.2 Liquid storage cabinets. Where other sections of this code require that liquid containers be stored in storage cabinets, such cabinets and storage shall be in accordance with Sections 404.3.2.1 through 3404.3.2.3. 3404.3.2.1.3 Doors. Doors shall be well fitted, self-closing and equipped with a three-point latch.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01387
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/11/2009 INSP - REINSPECTION JLOYA Approved Violations abated.