Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/17/2009

Applicant:

H L F PROPERTIES

Description:

Fire Prevention Inspection

Outstanding Inspections

Case Number: T09FR01330
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
04/17/2009 INSP - FULL DSIWARSK Violation Full Fire Inspection
04/17/2009 INSP - LIFE SAFETY DSIWARSK Violation IFC 605.1 Identified electrical hazards shall be abated. ____ Relocatable power tap needed in break room.
04/17/2009 INSP - LIFE SAFETY DSIWARSK Violation IFC 605.6 Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switches and electrical boxes. ____ Missing electrical box cover on East wall near desk. ____ Missing electrical box cover in back room by furnace. ____ Missing electrical box cover missing under table in break room.
04/17/2009 VIOL - FIRE PROTECTION SYSTEMS DSIWARSK Violation Comment: The building is rated as Type VB construction which does not require fire rated construction. However, it is strongly recommended that the hole in the ceiling in the back room be repaired to prevent rapid spread of fire in the ceiling if a fire occured.
04/17/2009 VIOL - FIRE PROTECTION SYSTEMS DSIWARSK Violation IFC 906.2 Portable fire extinguishers shall be installed and maintained in accordance with NFPA 10. ____ Portable fire extinguisher shall be serviced and mounted on wall or removed.