Fire Prevention Inspection

Outstanding Inspections

Case Number: T09FR01326
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
04/17/2009 INSP - FULL DSIWARSK Violation
04/17/2009 INSP - LIFE SAFETY DSIWARSK Violation IFC 605.5 Extension cords shall not substitute for permanent wiring. ____ Remove extension cord in front office by coffee pot.
04/17/2009 INSP - LIFE SAFETY DSIWARSK Violation IFC 605.6 Open junction boxes and open splices shall be prohibited. Approved covers shall be provided for all switches and electrical outlet boxes. ____ Electrical cover plate missing on electrical outlet box in back room on the ceiling.
04/17/2009 VIOL - MEANS OF EGRESS DSIWARSK Violation Comment: The building is rated as Type VB construction which does not require fire rated construction. However, it is strongly recommended that the large hole in the ceiling in the rear work area be repaired to prevent rapid spread of fire in the ceiling if a fire occured.
04/17/2009 VIOL - MEANS OF EGRESS DSIWARSK Violation IFC 1008.1.8 Egress doors shall readily openable from the egress side without the use of a key or special knowledge or effort. ____ Multiple locks on rear egress door must be removed.