Description:

Inspection

Outstanding Inspections

Case Number: T09FR01317
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
04/16/2009 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 505.1 Address requirements.
04/16/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Electrical breaker box door to be repaired.
04/16/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4 Multiplug adapter.
04/16/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Blanks in panel
04/16/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Open wiring splice.
04/16/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 Exit signs required at both exits.
04/16/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1028.2 Obstructed rear exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01317
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/19/2009 INSP - FULL TKNAPP Approved