Case: T09FR01317
Case Details
Entered Date:
04/16/2009
Applicant:
WILMOT PLAZA LC
Description:
Inspection
Outstanding Inspections
Case Number: T09FR01317
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2009 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 505.1 Address requirements. |
04/16/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Electrical breaker box door to be repaired. |
04/16/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 Multiplug adapter. |
04/16/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Blanks in panel |
04/16/2009 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Open wiring splice. |
04/16/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1011.1 Exit signs required at both exits. |
04/16/2009 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.2 Obstructed rear exit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01317
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2009 | INSP - FULL | TKNAPP | Approved |