Case: T09FR01315
Case Details
Entered Date:
04/16/2009
Applicant:
SANTA CRUZ PLAZA LLC
Description:
Foot locker full fire inspection.
Outstanding Inspections
Case Number: T09FR01315
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2009 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146 |
04/16/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01315
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2009 | INSP - REINSPECTION | JLOYA | Approved | Area around electrical panels cleared, no other fire code violations found. |