Case: T09FR01253
Case Details
Entered Date:
04/14/2009
Applicant:
BROADWAY POWERCENTER GROUP LLC
Description:
Subway Kelly Wymer 298-1188 Inspector M. Pursley
Outstanding Inspections
Case Number: T09FR01253
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2009 | INSP - FULL | MPURSLEY | Correction Required | Inital Inspection 4/13/09 Reinspection on or after 4/27/09 |
04/14/2009 | VIOL - BUILDING SVCS & SYSTEMS | MPURSLEY | Correction Required | 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. |
04/14/2009 | VIOL - FIRE PROTECTION SYSTEMS | MPURSLEY | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. -- ---Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed |
04/14/2009 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply, in the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ____Have emergency lighting tested/repaired. 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code ____Have exit sign tested/repaired. Re-inspection scheduled on or after ___/___/___ Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01253
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2009 | INSP - REINSPECTION | MPURSLEY | Approved |