Description:
Pinoy Fast Food 520-907-6897 Isaac Ohara Inspector M. Pursley
Outstanding Inspections
Case Number: T09FR01215
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2009 | INSP - FULL | MPURSLEY | Correction Required | Initial inspection 4/8/09 Reinspection 4/22/09 |
| 04/08/2009 | VIOL - PRECAUTION AGAINST FIRE | MPURSLEY | Correction Required | 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code. |
| 04/08/2009 | VIOL - BUILDING SVCS & SYSTEMS | MPURSLEY | Correction Required | 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. |
| 04/08/2009 | VIOL - FIRE PROTECTION SYSTEMS | MPURSLEY | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ___have hood system tested and tagged. |
| 04/08/2009 | VIOL - COMPRESSED GASES | MPURSLEY | Correction Required | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times Re-inspection scheduled on or after ___/___/___ Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01215
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2009 | INSP - REINSPECTION | MPURSLEY | Approved |