Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/07/2009

Applicant:

SANTA CRUZ PLAZA LLC

Description:

Rent A Center fire inspection.

Outstanding Inspections

Case Number: T09FR01191
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
04/07/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
04/07/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
04/07/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
04/07/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
04/07/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width.
04/07/2009 VIOL - MEANS OF EGRESS JLOYA Violation To ensure that there is no confusion on the required exiting from the building the following must be completed: 2. A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01191
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/28/2009 INSP - REINSPECTION JLOYA Approved After precitation was issued all violations were abated upon 2nd reinspection.