Case: T09FR01191
Case Details
Entered Date:
04/07/2009
Applicant:
SANTA CRUZ PLAZA LLC
Description:
Rent A Center fire inspection.
Outstanding Inspections
Case Number: T09FR01191
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2009 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146 |
04/07/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
04/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
04/07/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
04/07/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width. |
04/07/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | To ensure that there is no confusion on the required exiting from the building the following must be completed: 2. A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01191
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2009 | INSP - REINSPECTION | JLOYA | Approved | After precitation was issued all violations were abated upon 2nd reinspection. |