CRESTLINE INVESTMENTS LLC

Description:

Inspection

Outstanding Inspections

Case Number: T09FR01190
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
04/07/2009 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 508.5.4 CREAR SPACE AROUND CONTROL VALVES.
04/07/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 EMERGENCY LIGHT SHALL BE REPAIRED.
04/07/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 WORKING SPACE AROUND ELECTRICAL EQUIPMENT.
04/07/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 BLANKS SHALL BE INSTALLED IN PANEL LID3-2.
04/07/2009 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 MISSING CEILING TILE.
04/07/2009 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 EXTINGUISHER SHALL BE MOUNTED ON A HANGER.
04/07/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1028.2 HALLWAY AT NE EXIT SHALL NOT BE OBSTRUCTED.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01190
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/22/2009 INSP - FULL TKNAPP Approved