Case: T09FR01167
Case Details
Entered Date:
04/07/2009
Applicant:
LPR PROPERTIES LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR01167
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 04/08/2009 | VIOL - FIRE SERVICE FEATURES | MWAINWRI | Violation | 2006 IFC 504.2 INSTALL 2 SIGNS ON THE 2 REAR DOORS STATING "DOOR BLOCKED" |
| 04/08/2009 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.1 REPLACE MISSING OUTLET COVER PLATE BY PROOF BOX |
| 04/08/2009 | VIOL - FIRE RESIST.RATED CONST | MWAINWRI | Violation | 2006 IFC 703.1 REPLACE MISSING CEILING TILES |
| 04/08/2009 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 SERVICE AND TAG FIRE EXTINGUISHER BY OVENS (2) SERVICE ANT TAG FIRE EXTINGUISHER BY TIME CLOCK |
| 04/08/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT BY STORE ROOM REPAIR EMERGENCY LIGHT BY OFFICE DOOR |