Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/07/2009

Applicant:

GAMEZ FRANCISCO

Description:

Full Fire Prevention Inspection. Craig Schumacher Cell # 241-5140

Outstanding Inspections

Case Number: T09FR01165
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
04/07/2009 VIOL - ADMINISTRATION JBURGE Correction Required IFC Chapter 2 Definitions Storage Group S. Storage Group S occupancy includes, among others, the use of a building or structure, or a portion thereof, for storage that is not classified as a hazardous occupancy. _____1. Send a notice to all Studios informing the occupants that all beds shall be removed and that the building use is not classified for sleeping purposes. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
04/07/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and test the fire alarm system. NOTE: The alarm panel is showing trouble in zone A55.
04/07/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. _____1. Remove all storage from obstructing the EXIT doors.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01165
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/20/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been abated.