Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/07/2009

Applicant:

GAMEZ FRANCISCO

Description:

Full Fire Prevention Inspection. Craig Schumacher Cell # 241-5140

Outstanding Inspections

Case Number: T09FR01164
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
04/07/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove the storage from obstructing the working space of the electrical service equipment. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01164
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/27/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.