Case: T09FR01153
Case Details
Entered Date:
04/06/2009
Applicant:
DND NEFFSON CO
Description:
Full Fire Prevention Inspection Building Rep: Muhammad Muhammad Phone # 888-3265
Outstanding Inspections
Case Number: T09FR01153
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/06/2009 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
04/06/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels according to code. |
04/06/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Properly hang all portable fire extinguishers (2) according to the code below: 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). |
04/06/2009 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions hindering the use, the path, or the activity of the egress door and be sure to always maintain a clear and obstruction free path to your rear egress door. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ___________________ Passed on: ________ (Joseph P. Longo) |