Description:

pizza hut fire inspection.

Outstanding Inspections

Case Number: T09FR01114
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
04/01/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
04/01/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
04/01/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
04/01/2009 VIOL - COMPRESSED GASES JLOYA Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01114
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/16/2009 INSP - REINSPECTION JLOYA Approved All violations abated.