Description:

Full Fire Prevention Inspection Building Rep: Skip Pitney Phone # 293-7859

Outstanding Inspections

Case Number: T09FR01112
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
04/01/2009 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
04/01/2009 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____ Remove the electrical inhibiters that prevent your electrical box from breaking during a electrical hazard.
04/01/2009 VIOL - FIRE RESIST.RATED CONST JLONGO Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Replace the missing vent cover to comply with the fire code, reducing the escape of smoke and heat into the vents and the reducing the spread of fire.
04/01/2009 VIOL - MEANS OF EGRESS JLONGO Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards (x2) ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ___________________ Passed on: ________ (Joseph P. Longo)