Case: T09FR01102
Case Details
Entered Date:
03/30/2009
Applicant:
4-D PROPERTIES
Description:
La Salsa Margie Fenton Victor Calderon 520-747-0066 Inspector M. Pursley
Outstanding Inspections
Case Number: T09FR01102
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2009 | INSP - FULL | MPURSLEY | Correction Required | Full Inspection 3/30/09 C of O on file |
03/30/2009 | VIOL - PRECAUTION AGAINST FIRE | MPURSLEY | Correction Required | 315.2 Storage in buildings Storage of combustible materials shall be orderly. Storage shall be separated from heaters or heating devices so that ignition cannot occur. ____Keep hot water heater clear. 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. ____Keep sprinkler heads clear. |
03/30/2009 | VIOL - FIRE SERVICE FEATURES | MPURSLEY | Correction Required | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. ____Remove items from riser cage. |
03/30/2009 | VIOL - BUILDING SVCS & SYSTEMS | MPURSLEY | Correction Required | 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels according to code. |
03/30/2009 | VIOL - FIRE PROTECTION SYSTEMS | MPURSLEY | Correction Required | 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. ____fix screens on hood system. ____fix sprinkler escutcheon. |
03/30/2009 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. ____Provide proof of emergency lighting. |
03/30/2009 | VIOL - COMPRESSED GASES | MPURSLEY | Correction Required | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times |
03/30/2009 | VIOL - COMPRESSED GASES | MPURSLEY | Correction Required | Re-inspection scheduled on or after 4/14/09 Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01102
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2009 | INSP - REINSPECTION | MPURSLEY | Approved | Passed inspection, Deschaines still has T0 open for sprinkler system. |