Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/27/2009

Applicant:

MC DONALD S CORPORATION

Description:

Full Fire Prevention Inspection.

Outstanding Inspections

Case Number: T09FR01098
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
03/27/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.1- Remove the electrical breaker stop located on the breaker in the basement.
03/27/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3- Remove all storage from obstructing the electrical service equipment located in the basement.
03/27/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6- All open spaces in the electrical panels shall be properly covered.
03/27/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6- Provide the hood system inspection reports.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01098
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/05/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.