Case: T09FR01088
Case Details
Entered Date:
03/26/2009
Applicant:
WOODS MARVIN & SHARMON R CP/RS
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR01088
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2009 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Violation | 2006 IFC 315.2.2 REMOVE COMBUSTIBLE ITEMS IN THE EXIT CORRIDOR BACK HALL TO LIBRARY AND BLDG B. KEEP A 36 IN ISLE |
| 03/26/2009 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORDS IN ROOMS B1 AND B8 ] |
| 03/26/2009 | VIOL - FIRE SERVICE FEATURES | MWAINWRI | Violation | 2006 IFC 510.1 ID RISER ROOM WITH A SIGN STATING RISER ROOM |
| 03/26/2009 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.3 KEEP ELECTRICAL PANELS CLEAR OF OBSTRUCTIONS IN ELEC ROOM |
| 03/26/2009 | VIOL - FIRE RESIST.RATED CONST | MWAINWRI | Violation | 2006 IFC 703.1 REPLACE 2 MISSING CEILING TILES IN STORAGE ROOM |
| 03/26/2009 | VIOL - FIRE RESIST.RATED CONST | MWAINWRI | Violation | REPLACE CEILING TILE IN FA4 |
| 03/26/2009 | VIOL - FIRE RESIST.RATED CONST | MWAINWRI | Violation | REPLACE CILING TILE IN B4 CLOSET |
| 03/26/2009 | VIOL - FIRE RESIST.RATED CONST | MWAINWRI | Violation | REPLACE MISSING CEILING TILE IN SERVER ROOM |
| 03/26/2009 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 SERVICE AND TAG BOTH SPRINKLER SYSTEMS. ALSO REMOVE ITEMS IN RISER ROOM WHICH IS BLOCKING ACCESS TO THE SHUT OFF VALVE. |
| 03/26/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.3 REPAIR EXIT SIGN BY BACK HALL |
| 03/26/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.5 REPAIR EXIT/EMERGENCY SIGN AT ENTRANCE OF 24-7 LAB REPAIR EXIT/EMERGENCY SIGN IN AUDITORIUM |
| 03/26/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | REPAIR EMERGENCY LIGHT BY MENS/'WOMENS RESTROOM REPAIR EMERGENCY LIGHT IN ROOM FA3 |
| 03/26/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | REPAIR EMERGENCY LIGHTS BY ROOMS B7 REPAIR EMERGENCY LIGHT BY B4 |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01088
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2010 | INSP - FULL | MWAINWRI | Approved |