Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR01088
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
03/26/2009 VIOL - PRECAUTION AGAINST FIRE MWAINWRI Violation 2006 IFC 315.2.2 REMOVE COMBUSTIBLE ITEMS IN THE EXIT CORRIDOR BACK HALL TO LIBRARY AND BLDG B. KEEP A 36 IN ISLE
03/26/2009 VIOL - PRECAUTION AGAINST FIRE MWAINWRI Violation 2006 IFC 605.5 REMOVE EXTENSION CORDS IN ROOMS B1 AND B8 ]
03/26/2009 VIOL - FIRE SERVICE FEATURES MWAINWRI Violation 2006 IFC 510.1 ID RISER ROOM WITH A SIGN STATING RISER ROOM
03/26/2009 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.3 KEEP ELECTRICAL PANELS CLEAR OF OBSTRUCTIONS IN ELEC ROOM
03/26/2009 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation 2006 IFC 703.1 REPLACE 2 MISSING CEILING TILES IN STORAGE ROOM
03/26/2009 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation REPLACE CEILING TILE IN FA4
03/26/2009 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation REPLACE CILING TILE IN B4 CLOSET
03/26/2009 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation REPLACE MISSING CEILING TILE IN SERVER ROOM
03/26/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE AND TAG BOTH SPRINKLER SYSTEMS. ALSO REMOVE ITEMS IN RISER ROOM WHICH IS BLOCKING ACCESS TO THE SHUT OFF VALVE.
03/26/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.3 REPAIR EXIT SIGN BY BACK HALL
03/26/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.5 REPAIR EXIT/EMERGENCY SIGN AT ENTRANCE OF 24-7 LAB REPAIR EXIT/EMERGENCY SIGN IN AUDITORIUM
03/26/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation REPAIR EMERGENCY LIGHT BY MENS/'WOMENS RESTROOM REPAIR EMERGENCY LIGHT IN ROOM FA3
03/26/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation REPAIR EMERGENCY LIGHTS BY ROOMS B7 REPAIR EMERGENCY LIGHT BY B4

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01088
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/12/2010 INSP - FULL MWAINWRI Approved