Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/25/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevention Inspection. Margarita Parrin 690-2911

Outstanding Inspections

Case Number: T09FR01076
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
03/25/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1. Remove the electrical cube adapter located in the hearing aid room. NOTE: Replace it with a fused power strip.
03/25/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove the extension cord used to power the vending machine located in merchandise pick-up.
03/25/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the broken light switch cover located in Hardlines.
03/25/2009 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1. Replace the missing ceiling tiles located in the HR storage area. _____2. Replace the missing ceiling tiles in the women's restroom located in the tire storage area. _____3. Replace the missing ceiling tiles located in the communications room. _____4. Replace the missing ceiling tile located in the special order storage room. _____5. Replace the missing ceiling tiles located in Gentle Dental. _____6. Replace the missing ceiling tiles in the computer room located in Kathy's area.
03/25/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Service and tag the portable fire extinguisher located in the home fashions stock room. _____2. Service and test the self closing lid for the fuel storage container located in the tire storage/repair area. _____3. Service and tag the portable fire extinguisher located in the PMT area. _____4. Service and test the emergency generator and provide documentation of the test. _____5. Service and test the fire alarm system and provide documentation of the test. _____6. Service and test the rolling fire door located by the automotive counter and provide documentation of the test. _____7. Service, tag and mount the portable fire extinguihser located in Gentle Dental by the oxygen cylinders. _____8. Remove all lint from the automatic sprinkler heads located in Gentle Dental.
03/25/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double keyed lock from the west door located by the automotive counter.
03/25/2009 VIOL - COMPRESSED GASES JBURGE Correction Required IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Properly secure the compressed gas cylinder located in Kathy's area to prevent falling. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01076
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/05/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.