Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/18/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevention Inspection. Amber Duke 292-9291

Outstanding Inspections

Case Number: T09FR01008
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
03/18/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove the storage from obstructing the electrical service equipment located in the back room ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
03/18/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair the emergency lighting unit located in the back stock room. _____2. Repair the emergency lighting unit located in the display area by the bikini's. _____3. Repair the emergency lighting unit located by the register.
03/18/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. _____1. Remove all storage from obstructing the rear exit door.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01008
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/13/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.