Case: T09FR00971
Case Details
Entered Date:
03/16/2009
Applicant:
PLAZA AT WILLIAM CENTRE LLC (THE)
Description:
Full Inspection conducted 03/12/09 Re-inspection: 13/26/09 (or after) If you have any questions please call, 791-4502 I have received a copy of this report: __________________ Business Representative: Inspector: __________________, Captain: _____________ David Greenleaf, MA 23
Outstanding Inspections
Case Number: T09FR00971
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
03/12/2009 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ replace 3 missing escutcheons in work room _____ replace damaged celing tile in office |
03/12/2009 | VIOL - MEANS OF EGRESS | DGREENLE | Correction Required | TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Repair/replace emergency egress light in workroom. |
03/12/2009 | VIOL - MEANS OF EGRESS | DGREENLE | Correction Required | TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit sign over East door |
03/16/2009 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Correction Required | TFC 315.2.1 - Ceiling clearance. Storage shall be maintained ... a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ above shelving in workroom |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00971
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2009 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: ON FILE & POSTED Extinguishers serviced 3/08 Sprinkler System inspected 10/31/08, NO Deficiencies noted FDC and Lock Box located center of East Wall. Riser room in back hallway of Coldwell Banker Key checked 12/31/08 |