Description:

Full Inspection conducted 03/12/09 Re-inspection: 13/26/09 (or after) If you have any questions please call, 791-4502 I have received a copy of this report: __________________ Business Representative: Inspector: __________________, Captain: _____________ David Greenleaf, MA 23

Outstanding Inspections

Case Number: T09FR00971
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
03/12/2009 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
03/12/2009 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Correction Required TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ replace 3 missing escutcheons in work room _____ replace damaged celing tile in office
03/12/2009 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Repair/replace emergency egress light in workroom.
03/12/2009 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit sign over East door
03/16/2009 VIOL - PRECAUTION AGAINST FIRE DGREENLE Correction Required TFC 315.2.1 - Ceiling clearance. Storage shall be maintained ... a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. _____ above shelving in workroom

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00971
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/12/2009 INSP - FULL DGREENLE Approved Certificate of Occupancy: ON FILE & POSTED Extinguishers serviced 3/08 Sprinkler System inspected 10/31/08, NO Deficiencies noted FDC and Lock Box located center of East Wall. Riser room in back hallway of Coldwell Banker Key checked 12/31/08