Case: T09FR00970
Case Details
Entered Date:
03/16/2009
Applicant:
NEIL O KLEINMAN EXEMPT TR &
Description:
Full Fire Prevention Inspection. Hector Heras 296-9655
Outstanding Inspections
Case Number: T09FR00970
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5- Remove the extension cord used to power the warmer table. NOTE: Replace the extension cord with a fused power-strip. |
| 03/16/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Service and tag both hood extinguishing systems. |
| 03/16/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3- Clean and remove all grease accumulation from the kitchen hoods. |
| 03/16/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Test all emergency lighting units and exit signs for emergency back-up power. NOTE: Repair or replace any defective exit sign or lighting unit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00970
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |