Case: T09FR00933
Case Details
Entered Date:
03/12/2009
Applicant:
RAYMOND OBULIA
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR00933
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2009 | INSP - FULL | JVINCENT | Violation | FULL FIRE INSPECTION |
| 03/12/2009 | VIOL - ADMINISTRATION | JVINCENT | Violation | TFC 102.3 1) PROVIDE COFO. |
| 03/12/2009 | VIOL - BUILDING SVCS & SYSTEMS | JVINCENT | Violation | TFC 605.1 1) COVERPLATE NEEDED FOR ELECTRICAL OUTLET IN DINING ROOM. 2) REPAIR LIGHT IN BEDROOM #4. EXPOSED ELECTRICAL. |
| 03/12/2009 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | TFC 903.2.7 1) SPRINKLER SYSTEM REQUIRED BY 10/22/2010. |
| 03/12/2009 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | TFC 907.3.1.8 1) LOCAL FIRE ALARM REQUIRED IF COFO DATED AFTER SEPT 24, 2001. |
| 03/12/2009 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | TFC 1008.1.8 1) REMOVE DOUBLE KEYED LOCK FROM LAUNDRY ROOM EXIT. THIS DOOR IS USED AS THE MAIN DOOR/EXIT. REPLACE WITH A THUMBTURN LOCK. |
| 03/12/2009 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | TFC 1011.1 1) BOTH REQUIRED EXITS NEED EXIT SIGNS. |
| 03/12/2009 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | TFC 1027.5 1) EMERGENCY LIGHTING UNITS NEEDS FOR MEANS OF EGRESS ILLUMINATION DURING POWER LOSS. |