Case: T09FR00809
Case Details
Entered Date:
03/04/2009
Applicant:
PARK MALL LLC
Description:
Initial FPI -- Annie's Hallmark #408
Outstanding Inspections
Case Number: T09FR00809
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2009 | VIOL - ADMINISTRATION | DGREENLE | Correction Required | SECTION 107, MAINTENANCE TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. _____ Exit Sign Illumination _____ Repair Emergency Light |
03/02/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Replace with approved power strip. |
04/10/2009 | INSP - REINSPECTION | DGREENLE | Continued | Electrician Bob Blizzard has parts on order for overhead emergency lights. Call to schedule RI |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00809
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2009 | INSP - FULL | DGREENLE | Approved | NOTE: there are 2 C of O's for this occupancy. There is a sprinklered loft/mezzanine in the stockroom area. |