Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/03/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevention Inspection. Christine Olvera 292-1695

Outstanding Inspections

Case Number: T09FR00798
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
03/03/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove the storage from obstructing the electrical service equipment located in the back room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
03/03/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Service and tag the portable fire extinguisher.
03/03/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. _____1. Properly mount the portable fire extinguisher.
03/03/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Test all emergency lighting units and exit signs for emergency back-up power and repair any deficiencies. NOTE: Provide documentation of the testing.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00798
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/05/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.