Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/27/2009

Applicant:

RIVERDANCE LTD PARTNERSHIP

Description:

Full Fire Prevention Ispection. Bill Negunt 623-2664

Outstanding Inspections

Case Number: T09FR00781
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
02/27/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC505.1 Address numbers. (cot mod) New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. _____1. Comply with Pima County Address Display Requirements.
02/27/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove the extension cords used to power the neon signs located in the south windows.
02/27/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. All portable fire extinguishers shall be serviced anually. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
02/27/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. _____1. All portable fire extinguihsers shall be properly mounted.
02/27/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.3.5 Security grilles. In Groups B, F, M and S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. Where two or more means of egress are required, not more than one-half of the exits or exit access doorways shall be equipped with horizontal sliding or vertical security grilles. _____1. Remove the security grills from all exit doors.
02/27/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double-keyed locks from all exterior doors and replace them with thumb-turn locks. NOTE: The main entrance can remain Double-keyed.
02/27/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____1. Remove the EXIT sign located outside in the patio area that leads occupants back into the building.
02/27/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC Section 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1. Remove the double-keyed lock from the southeast exit door with panic hardware.
02/27/2009 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be secured by the following method: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. _____1. Properly secure all compressed gas cylinders to prevent falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00781
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/06/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.