Case: T09FR00757
Case Details
Entered Date:
02/25/2009
Applicant:
DND NEFFSON CO
Description:
Full Fire Prevention Inspection. Pam Luna 888-5273
Outstanding Inspections
Case Number: T09FR00757
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove the storage from obstructing the electrical service equipment located in the electrical room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
02/25/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Test all emergency lighting units and EXIT signs for emergency back-up power. NOTE: Provide documentation of the testing and repair any deficiencies found. |
02/25/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. _____1. Remove all storage from obstructing the exit doors located in the back rooms. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00757
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/24/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |