Case: T09FR00735
Case Details
Entered Date:
02/23/2009
Applicant:
LA COLONIA SEIS APARTMENTS LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR00735
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2009 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Violation | 2006 IFC 315.2.3 REMOVE PROPANE HEATER BEING STORED IN ELECTRICAL RM REMOVE ALL OTHER ITEMS STORED IN ELECTRICAL ROOM |
02/23/2009 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 SERVICE AND TAG FIRE EXTINGUISHER IN ELEVATOR LOBBY |
02/23/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.5 REPAIR THE EMERGENCY LIGHTS IN THE FOLLOWING AREAS SE STAIRS BETWEEN FLOOR 1&2 SE STAIRS BETWEEN FLOOR 2&3' SE STAIRS ON 3RD FLOOR ALL 4 EMERGENCY LIGHTS ON 3RD FLOOR BALCONY NE STAIRS 3RD FLOOR NE STAIRS BETWEEN 2&3 FLOORS NE STAIRS ON 2ND FLOOR NE STAIRS BETWEEN 1&2 FLOORS NE STAIRS ON 1ST FLOOR NE ELEVATOR LOBBY |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00735
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2009 | INSP - FULL | MWAINWRI | Approved |