INSPECTION

Entered Date:

02/23/2009

Applicant:

LA COLONIA SEIS APARTMENTS LLC

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR00735
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
02/23/2009 VIOL - PRECAUTION AGAINST FIRE MWAINWRI Violation 2006 IFC 315.2.3 REMOVE PROPANE HEATER BEING STORED IN ELECTRICAL RM REMOVE ALL OTHER ITEMS STORED IN ELECTRICAL ROOM
02/23/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE AND TAG FIRE EXTINGUISHER IN ELEVATOR LOBBY
02/23/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.5 REPAIR THE EMERGENCY LIGHTS IN THE FOLLOWING AREAS SE STAIRS BETWEEN FLOOR 1&2 SE STAIRS BETWEEN FLOOR 2&3' SE STAIRS ON 3RD FLOOR ALL 4 EMERGENCY LIGHTS ON 3RD FLOOR BALCONY NE STAIRS 3RD FLOOR NE STAIRS BETWEEN 2&3 FLOORS NE STAIRS ON 2ND FLOOR NE STAIRS BETWEEN 1&2 FLOORS NE STAIRS ON 1ST FLOOR NE ELEVATOR LOBBY

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00735
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/18/2009 INSP - FULL MWAINWRI Approved