Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/23/2009

Applicant:

BARCLAY CRESWIN RETAIL LLC

Description:

Fashion bug fire inspection.

Outstanding Inspections

Case Number: T09FR00734
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
02/23/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels
02/23/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
02/23/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path leading to rear exit, and maintain it this way.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00734
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
02/23/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
03/09/2009 INSP - REINSPECTION JLOYA Approved All violations abated