Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR00733
Case Details
Entered Date:
02/23/2009
Applicant:
BARCLAY CRESWIN RETAIL LLC
Description:
Contours fire inspection.
Outstanding Inspections
Case Number: T09FR00733
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2009 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146 |
02/23/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
02/23/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00733
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2009 | INSP - REINSPECTION | JLOYA | Approved | Business no longer open. All eqipment gon from local. |