El Guero canelo fire inspection
Outstanding Inspections
Case Number: T09FR00725
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2009 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146 |
| 02/20/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 603.5.2 Heating appliance installation. Heating appliances shall be installed in accordance with the manufacturer's instructions, the International Building Code, the International Mechanical Code, the International. |
| 02/20/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
| 02/20/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
| 02/20/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
| 02/20/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 609.2 Where required, A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. |
| 02/20/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. |
| 02/20/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. |
| 02/20/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way. |
| 02/20/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting |