Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/19/2009

Applicant:

BARCLAY CRESWIN PROPERTIES I LLC

Description:

Starbucks fire inspection

Outstanding Inspections

Case Number: T09FR00696
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
02/19/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.
02/19/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00696
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
02/19/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
03/09/2009 INSP - REINSPECTION JLOYA Approved All violations abated.