Case: T09FR00694
Case Details
Entered Date:
02/19/2009
Applicant:
BARCLAY CRESWIN RETAIL LLC
Description:
Salon De Futur fire inspection.
Outstanding Inspections
Case Number: T09FR00694
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code. |
02/19/2009 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00694
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2009 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146 |
03/09/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated |