Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR00643
Case Details
Entered Date:
02/18/2009
Applicant:
DND NEFFSON CO
Description:
Full Fire Prevention Inspection. Christina White 888-4294
Outstanding Inspections
Case Number: T09FR00643
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/18/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove the storage from obstructing the electrical service equipment located in the back room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
02/18/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Test all emergency lighting units and exit signs for emergency back-up power and repair or replace any deficiencies. NOTE: provide documentation of the test and repairs made. |
02/18/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. _____1. Remove the storage from obstructing the rear exit door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00643
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |