Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/17/2009

Applicant:

WESTERN ROUND INC & KREGER ALAN W

Description:

Arby's full fire inspection.

Outstanding Inspections

Case Number: T09FR00622
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
02/17/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
02/17/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00622
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/17/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146