Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/17/2009

Applicant:

ADMINISTRATIVE ADDRESSES

Description:

Walgreens full fire inspection.

Outstanding Inspections

Case Number: T09FR00618
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
02/17/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
02/17/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
02/17/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
02/17/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ___ Remove locking mecahnisms and locking hardware from emergency exits.
02/17/2009 VIOL - COMPRESSED GASES JLOYA Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00618
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/05/2009 INSP - REINSPECTION JLOYA Approved All violations abated.