Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/17/2009

Applicant:

FURBER DEVELOPMENT

Description:

Big5 full fire inspection.

Outstanding Inspections

Case Number: T09FR00616
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/17/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
02/17/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
02/17/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code.
02/17/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00616
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
02/17/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
03/05/2009 INSP - REINSPECTION JLOYA Approved All violations abated.