Case: T09FR00607
Case Details
Entered Date:
02/13/2009
Applicant:
CHRIST CHURCH UNITED METHODIST INC
Description:
BUSINESS INSPECTION
Outstanding Inspections
Case Number: T09FR00607
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2009 | INSP - FULL | EDESCHAI | Correction Required | DURING THE INSPECTION OF YOUR BUSINESS THE FOLLOWINF DEFICIENCIES WERE FOUND. 1) 605.5 EXTENTION CORDS THE FOLLOWING AREAS HAD EXTENTION CORDS IN USE, AT THE MICRO WAVE IN THE KITCHEN, ROOM 17-AT THE REFRIGERATOR AND COFFEE POT( THIS IS RUNNING UNDER A CLOSET DOOR TO AN OUTLET IN THE CLOSET, THE BUSINESS OFFICE. 2) 504.2 MAINTENANCE OF EXTERIOR DOORS THE EXIT DOOR (S/E) AT THE SOUTH STAIR WELL IS STICKING 3) 807.4.3.1 ART WORK ART WORK AND TEACHING AIDS SHALL NOT BE HUNG REOM CEILINGS IN CLASSROOMS 4) 315.2.3 EQUIPMENT ROOMS THE STORAGE SHALL NOT BE STORED IN THE FURNACE ROOM OF THE SUPERNTENDANTS OFFICE 5) 904.11.6.3 EXAUST HOODS PROVIDE DOCUMENTATION FOR THE CLEANING OF THE KITCHEN EXAUST HOOD. A REINSPECTION WILL BE PERFORMED IN APPROXMATELY 30 DAYS. |