Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/10/2009

Applicant:

SOLORZANO TEOFILO & NINFA JT/RS

Description:

Jalisco restaurant full fire inspection

Outstanding Inspections

Case Number: T09FR00569
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
02/10/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring
02/10/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
02/10/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
02/10/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
02/10/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request.
02/10/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign __ Provide such signs for the rear emergency exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00569
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
02/10/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
03/17/2009 INSP - REINSPECTION JLOYA Approved All violations abated