Case: T09FR00563
Case Details
Entered Date:
02/10/2009
Applicant:
BARCLAY CRESWIN RETAIL LLC
Description:
Anna's linens full fire inspection.
Outstanding Inspections
Case Number: T09FR00563
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
02/10/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00563
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2009 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146. |
03/02/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated |