Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/10/2009

Applicant:

BARCLAY CRESWIN RETAIL LLC

Description:

Anna's linens full fire inspection.

Outstanding Inspections

Case Number: T09FR00563
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
02/10/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
02/10/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00563
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
02/10/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146.
03/02/2009 INSP - REINSPECTION JLOYA Approved All violations abated