Case: T09FR00562
Case Details
Entered Date:
02/10/2009
Applicant:
BARCLAY CRESWIN RETAIL LLC
Description:
Pets Mart full fire inspection.
Outstanding Inspections
Case Number: T09FR00562
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2009 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146 |
02/10/2009 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 309.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR00562
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated |