Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/06/2009

Applicant:

RODRIGUEZ ALBERT ARTHUR & GLORIA H JT/RS

Description:

La costa brava full fire inspection.

Outstanding Inspections

Case Number: T09FR00533
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
02/06/2009 INSP - FULL JLOYA Violation Correct the.146 following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146
02/06/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
02/06/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment.
02/06/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
02/06/2009 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. ____ Remove security door blocking emergency exit.
02/06/2009 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building.
02/06/2009 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
02/06/2009 VIOL - FLAMMABLE GASES JLOYA Violation 3503.1.1 Special limitations for indoor storage and use. Flammable gases shall not be stored or used in Group A, B, E, I or R ocupancies. ___Remove LP gas tank located in main dining area.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00533
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/17/2009 INSP - REINSPECTION JLOYA Approved All violations abated